IEC 60364-7-710 (BS 7671 Section 710)

Low-voltage electrical installations, Requirements for special installations: medical locations

In plain words

What it covers.

The wiring standard for medical locations. It classifies rooms as Group 0, 1 or 2 by how applied parts are used and how dangerous a loss of power would be. Group 2 locations, such as theatres and intensive care, need medical IT systems with insulation monitoring, supplementary equipotential bonding and safety power supplies.

Who uses it: Electrical designers, installers, estates engineers and clinical engineers specifying theatres and critical care.

A summary written by BMEssentia for learning, not the text of the standard. Always work from the current official edition and the manufacturer's instructions.

It covers

  • Group 0, 1 and 2 medical locations
  • Medical IT systems and insulation monitoring devices
  • Supplementary equipotential bonding
  • RCD use
  • Safety services supply and changeover time
  • Inspection and testing

Key points

What engineers need to know.

  • Group 0: no applied parts. Group 1: applied parts, but not to the heart. Group 2: intracardiac or life-critical procedures.
  • Group 2 uses medical IT systems so a first insulation fault raises an alarm instead of tripping the supply.
  • An insulation monitoring device warns staff at a set threshold, often 50 kohm.
  • Supplementary equipotential bonding keeps exposed metal parts at the same potential.
  • Safety supplies for critical lighting and equipment must change over within about 0.5 s or 15 s by class.
  • Room group is decided with clinical staff, based on the procedures done there.

Medical City

Where you practise it.

  • Room Builder medical electrical installations
  • Hospital Architect electrical groups
  • S2-M021 power infrastructure audit
  • S2-M056 electrical installation review